Section 130: General safety requirements

Central Electricity Authority (Measures relating to Safety and Electric Supply) Regulations, 2023Central Regulations · 2003

(1) A wire mesh shall be provided beneath the walk way; wherever constructed above the hanging valves in the valve hall.

146 THE GAZETTE OF INDIA : EXTRAORDINARY [PART III—SEC.4]

(2) Cables used for sensitive measurements shall be laid in separate and completely screened or covered channels or galvanised steel pipes.

(3) A separate emergency source of illumination with automatic initiation shall be provided in every room or compartment of high voltage direct current station.

(4) No oil immersed apparatus shall be kept within the valve hall.

(5) All doors of compartments containing modules equipped with laser diodes and junction boxes of the fibre optic cables shall be locked and marked with laser warning symbols.

Where this provision sits

ActCentral Electricity Authority (Measures relating to Safety and Electric Supply) Regulations, 2023
Section130
Marginal noteGeneral safety requirements
JurisdictionCentral
StatusIn force as published by the source

Find the provision, not just read it

The full text above is free, and it stays free. What a free CourtMesh account adds is everything you cannot do by reading one page at a time:

  • Search 49,000+ Central and State enactments by what a provision says, not by its number
  • Jump from any section to every judgment that has applied it
  • Search 300 million+ Indian court records alongside the statute
  • Ask a research agent to find and read the case law on a provision for you

Free account. No card. About a minute to create.

Create a free account

Need this as data, not as a page? Central Electricity Authority (Measures relating to Safety and Electric Supply) Regulatio… is one of 49,000+ enactments on CourtMesh. The Indian court cases API serves the case law that cites these provisions over JSON, with API documentation and plans and pricing. See also the judgment library.