Central Electricity Authority (Measures relating to Safety and Electric Supply) Regulations, 2023Central Regulations · 2003
(1) A wire mesh shall be provided beneath the walk way; wherever constructed above the hanging valves in the valve hall.
146 THE GAZETTE OF INDIA : EXTRAORDINARY [PART III—SEC.4]
(2) Cables used for sensitive measurements shall be laid in separate and completely screened or covered channels or galvanised steel pipes.
(3) A separate emergency source of illumination with automatic initiation shall be provided in every room or compartment of high voltage direct current station.
(4) No oil immersed apparatus shall be kept within the valve hall.
(5) All doors of compartments containing modules equipped with laser diodes and junction boxes of the fibre optic cables shall be locked and marked with laser warning symbols.
Need this as data, not as a page? Central Electricity Authority (Measures relating to Safety and Electric Supply) Regulatio… is one of 49,000+ enactments on CourtMesh. The Indian court cases API serves the case law that cites these provisions over JSON, with API documentation and plans and pricing. See also the judgment library.