Central Electricity Authority (Measures relating to Safety and Electric Supply) Regulations, 2023Central Regulations · 2003
(1) A separate emergency source of illumination with automatic initiation shall be provided in every room or campartment of gas insulated substation.
(2) Cable cover protection unit shall be provided between flanges of gas insulated substation and cable termination unit.
(3) Gas insulated substation installation of 220 kV and above voltage shall be provided with partial discharge monitoring system.
(4) SF6 gas leakage rate from any single compartment of gas insulated substation to atmosphere and between compartments shall not exceed as stipulated in the relevant standards.
Need this as data, not as a page? Central Electricity Authority (Measures relating to Safety and Electric Supply) Regulatio… is one of 49,000+ enactments on CourtMesh. The Indian court cases API serves the case law that cites these provisions over JSON, with API documentation and plans and pricing. See also the judgment library.