(1) (a) Two separate exists not opening on the same thoroughfare of public passage, shall be provided from the stage and from the Auditorium floor and from every tier which accommodates not more than 500 individuals; and where the Auditorium floor or any tier acconunodates more than SOO individuals, exit shall be provided at the rate of one for every 250 individuals, and one for any less number in excess.
Each of such exits shall be of not less than 1.5 meters in width between the leaves of the door when open.
(b) Jn case of Multiplex cinema, the entry and exits in each screen should be seperate from each other.
4-6 GUJARAT GOVERNMENT GAZETTl EX,. 7-1-2014 [PARTIV-B
(2) A corrunon place of aggress may serve as the exits for the floor of the auditorium and the first tier, provided its capacity be equal to the aggregate capacity prescribed by sub-rule (1) for the necessary outlets from such floor and tier.
(3) For any auditorium floor or any tier which does not accorrunodate more than 300 individuals, two
1.2 meters exits shall be considered sufficient.
(4) If any auditorium floor or any tier shall be divided into two or more parts, exits as prescribed in sub-rule (1) shall be provided for each such part.
(5) The licensee of the cinema shall not prevent the public to leave by any exits door.
(6) Every cinema house shall be equipped with sufficient number of IP based CCTV cameras in accordance with the directions of the State Government.