(1) All suspended fittings shall be firmly fixed.
(2) Combined gas and electric fittings shall not be used.
(3) Any electric light pendants or brackets in the auditorium and in front of the cinema or multiplex building generally shall be at least two and half meters above the floor to the lowest projecting part of the fittings. No electrical fittings or apparatus of any description shall be so fixed or arranged as to interfere at any time with the proper working of the safety curtain.
(4) (i) The electrical installation shall be incharge of a properly qualified person holding a Wireman’s or Supervisor’s permit issued by the Licensing Advisory and Examination Board of the Government of Karnataka or shall be incharge of a licensed Electrical Contractor whose name shall be intimated to the Electrical Inspector of the district or area.
(ii) Licensed Electrical Contractor shall furnish insulation resistance of all circuits and values of earth electrode annually to Electrical Inspector of the district.
(5) Instructions both in English, Hindi and in regional languages for the restoration of persons suffering from electric shock shall be affixed in a conspicuous place and at least one pair of rubber gloves in good order shall be provided for use of the wiremen.
(6) Earthing shall be done efficiently and perfectly as per Electricity Act 2003, Central Electricity Authority (measures relating to Safety and Electric Supply) Regulations, 2010 and rules and regulations thereafter, I S S 3043/1987 and shall be maintained properly. Earth electrodes shall be kept exposed and enclosed in masonry enclosures as per I.S. standards so as to facilitate watering, inspection and periodical testing.
71. Generator/alternate source of supply._ Where the supply of current is derived from special plant on the premises, such plant should in all cases be approved by the Electrical Inspector of the district or area.