(I) If any accident occurs in connection with the generation, transmission, supply or use .of electricity or in connection with, any part of the .electric lines or other works of any person and the accidents results in or is likely to have resulted in loss of human or animal life or many injury, to a human being or an anirrial, such person or any authorized person of the generating company or licensee, not below the rank of a WTI 4 01) lgullTOT 0,444, fiicn 24 ‘i 2016 • 857 Junior Engineer or equivalent shall intimate to the Inspector through telephone/fax within 24 hours of the knowledge .of the occurrence of the fatal accident and send a report in writing in the Form appended to these rules within 48 hours of the knowledge of occurrence of fatal And all other accidents. Where possible a telephonic 'message or e-mail should also be sent to the Inspector immediately, as soon as accident comes to the knowledge of the authorized officer of the generating company/ licensee or other person concerned.
(2) For the intimation of the accident, telephone numbers and fax numbers of Chief Electrical Inspector, Electrical. Inspector, District Collector, Police Station, Fire Brigade and nearest hospital shall be displayed at the conspicuous place in the generating station, switching. sub-station or station or sub-station and maintained in the .office of the incharge/owner of the Medium Voltage (MV) or High Voltage (HV) or Extra High Voltage (EHV) installations:
Provided that the telephone numbers, alternative numbers, fax numbers and e-mail address on which information of the accidents is required to be sent, shall be displayed on the website of the office of the Chief Electrical Inspector.