Section 5: Multi-storeyed Building

Development Control Regulations for Erode/Veuore/Tiruveuore/Coimbatore/Madurai/Gummudipoondi/Kancheepuram/Salem/Chengalpattu/Tiruppur/Tiruc…State Regulations of Tamil Nadu · 1971

"Multi-storeyed building" means a building exceeding 4 floors (including ground floor or if this ground floor is used for parking under stilts, stilt floor + 4 floors) whose height is 15 m. or more.

https://www.manupatrafast.com/pers/viewdoctoc.aspx?sPath=Bare%20Acts%20and%20Rules/State/tamil%20nadu/Rules/tamil%20nadu/tamil%20nadu%20town%20and%20country%20planning%20act%201971/DeCoReErVeGuKaSaChTiLoPlAr/DeCoReErVeGuKaSaChTiLoPlAr.htm&col=8Vmp9ozFMb/2ISz1SdixCIRVngsjs/j1lxFukHhUlVjtLjdB0bd4mmFTJWUx/aBSKBdGFQIME6VoesAFaCGBewHrWR8ddcNQuL7JwN7hYU7qHizMrFQj4LFUvb7Bkchar(43)6o706GyNkh4BCUcuVcjmbGhejF08ykNubEvKW4zqo890cktJ88vxBo32cc1YJmu9Dc/5IUlIm3BdNjSABchar(43)2R9TRHZChuWg9X1a6Zdqtl8E2/Y=#F2 https://www.manupatrafast.com/TOC/TocDisplay.aspx?col=8Vmp9ozFMb/2ISz1SdixCIRVngsjs/j1lxFukHhUlVjtLjdB0bd4mmFTJWUx/aBSKBdGFQIME6VoesAFaCGBewHrWR8ddcNQuL7JwN7hYU7qHizMrFQj4LFUvb7Bkchar(43)6o706GyNkh4BCUcuVcjmbGhejF08ykNubEvKW4zqo890cktJ88vxBo32cc1YJmu9Dc/5IUlIm3BdNjSABchar(43)2R9TRHZChuWg9X1a6Zdqtl8E2/Y=&path=Bare%20Acts%20and%20Rules/State/tamil%20nadu/Rules/tamil%20nadu/tamil%20nadu%20town%20and%20country%20planning%20act%201971/DeCoReErVeGuKaSaChTiLoPlAr/Toc.htm#to

(1) (a) Site Extent.-- The minimum extent of site for construction of multistoreyed building shall not be less than 1,500 square metres.

(b) Road width.-- The site sh3all either abut on a road not less than 18 metres in width or gain access from public road not less than 18 metres in width through a part of the site which can be treated as an exclusive passage of not less than 18 metres in width:

Provided further that multi-storeyed building may be permitted with limitations on maximum FSI and maximum height of the building on a site abutting or gaining access from a public road of minimum 12 metres/15 metres in width, or gain access from public road not less than 12metres/15metres in width through a part of the site which can be treated as an exclusive passage of not less than 12 metres/15 metres in width, subject to compliance of the planning parameters stated in the Table subregulation (2) below.

(c) Minimum road width of 12 metre or above shall be permissible with multi-storeyed buildings without any further procedures. The height of multi-storeyed buildings will be technically correlated with the width of the abutting road. Once the road width is established based on records, these areas may be permitted with multistoreyed buildings. Special consideration may be given to any specific recommendation to the contrary of above rule. No further resolutions or otherwise will be required. In case of doubts or clarification or any related issue, Empowered Committee shall take a final decision.

Explanation.-- Road width means whole extent of space within the boundaries of the road/street measured at right angles to the course of direction of such road/street. The qualifying road width for permitting multi-storeyed building shall be available at least for a stretch of 500 metres along the length of the road abutting the site and the stretch from a junction can be straight or a curve or zigzag or combination of the above.

To cite examples:--

(a) If the road over its general length is of 18 metres width, but because of some kinks in front of the site one end is 17.8 metres and the other end is 18.2 metres is acceptable.

(b) If the general road is of width less than 18 metres width, but only widens opposite to or nearer to the site is more than 18 metres, is not acceptable.

(c) If the road is generally of 18 metres width upto a considerable length on one side, but discontinues and narrows into a road of smaller width on the other side of the site in question and the plot owner is willing to leave enough space for continuity of 18 metres road in front of his site, this will have to be checked and decided on case-by-case. This should be referred to Empowered Committee for appropriate decision.

(d) If the general road width is less than 18 metres and the site owner merely agrees to leave enough space to have 18 metres in front of his site only, this is not acceptable.

(2) The extent of the site, FSI, set back, etc., for multi-storeyed Building shall be regulated according to the Table below:-- Sl.

No.

Description. Category 1(a).

Category 1(b).

Category II.

Category III.

A: Minimum plot extent.

1200 sq.

m.

1200 sq.

m.

1500 sq.

m.

2500 sq. m.

B. Minimum Plot width/frontage.

25 m. 25 m. 25 m. 40 m.

C. Minimum road width.

12 m. 15 m. 18 m.

P. Maximum FSI. 1.5 1.75 2.50 2.25 2.00 E. Maximum coverage.

30% 30% 30% Above 30% upto 40%.

Above 40% upto 50%.

F. Maximum height above Ground Level.

G + 6 or Stilt + 7 floors subject to a maximum 24 m.

G+8 Stilt + 9 floors subject to a maximum 30 m.

60 metre where the width of the abutting road is minimum 18 metre, and exceeding 60 metre where the width of abutting road is minimum 30.5 metres, subject to such conditions as may be necessary. 2[In case of Hospital buildings, the maximum permissible height is 30 metres.]

Height of the building above ground level Minimum required setback space from the property boundary.

G. Minimum set back all around.

Above 15 m. up to 30 m.

7 m.

Above 30 m. For every increase in height of 6 m. or part thereof above 30 m.

minimum extent of setback space to be left additionally shall be one metre.

H. Spacing between block in case of group developments.

Height of the building above ground level.

Minimum required spacing between blocks.

Above 15 m. up to 30 m.

7 m.

Above 30 m. For every increase in height of 6 m. or part thereof above 30 m. space to be left additionally shall be one metre.

Note: (i) The space specified above shall be kept open to sky and free from any erection/projection (such as sunshade/balcony) of any building other than a fence or compound wall provided that these open yards may be used for the provision of access ways to the building's parking facilities.

https://www.manupatrafast.com/pers/viewdoctoc.aspx?sPath=Bare%20Acts%20and%20Rules/State/tamil%20nadu/Rules/tamil%20nadu/tamil%20nadu%20town%20and%20country%20planning%20act%201971/DeCoReErVeGuKaSaChTiLoPlAr/DeCoReErVeGuKaSaChTiLoPlAr.htm&col=8Vmp9ozFMb/2ISz1SdixCIRVngsjs/j1lxFukHhUlVjtLjdB0bd4mmFTJWUx/aBSKBdGFQIME6VoesAFaCGBewHrWR8ddcNQuL7JwN7hYU7qHizMrFQj4LFUvb7Bkchar(43)6o706GyNkh4BCUcuVcjmbGhejF08ykNubEvKW4zqo890cktJ88vxBo32cc1YJmu9Dc/5IUlIm3BdNjSABchar(43)2R9TRHZChuWg9X1a6Zdqtl8E2/Y=#F2

(ii) A watchman or caretaker booth or Kiosk not exceeding

2.5 m. x 2.5 m. in size at each gate and not exceeding 3 metre in height, or power/transformer room not exceeding 4 metre in height shall be permitted in the set backspace at ground level after leaving 7 metres clear set back from the main structure. Provided that the height restriction shall not apply for an open transformer.

(iii) Gate pillars without or with arches with a minimum headroom clearance of 5.50 metre at least to a width of 3.5 metre, may be permitted in the set back space after leaving 7 metres clear set back from the main structure.

(iv) In the cases where street alignment has been prescribed, the front open space shall be left from the street alignment.

(v) In cases of hospital buildings, an additional Floor Space Index of 0.25 is allowable over and above the normally permissible FSI.

(vi) The Floor Space Index for Information Technology development shall be allowed at 1.5 times of the FSI ordinarily permissible for respective use of that zone provided the site extent is not less than 2,000 sq. m. This benefit will not be available for primary residential use zone.

Explanations.--

(1) Parking and par3king facilities.

For the use of the occupants and of persons visiting the premises for the purposes of profession, trade, business, recreation or any other activity, parking spaces and parking facilities shall be provided within the site to the satisfaction of the Authority and conforming to the standards specified in Schedule-II.

(2) Vehicular access within the site.

Internal vehicular access way including passage, if any, within the site, shall have a clear width of 7.2 metre and such vehicular access shall be available for every building block in the site. Further, it shall be a clear width of open to sky and no projection in structure over it is permissible.

(3) Corridor width.-- The corridor serving as access for units in the development in whichever floor they may be situated shall not be less than the standards prescribed in the Table below:-- TABLE Sl.

No.

Building use or type. Minimum width of corridor.

(i) Residential buildings. 1.0 metres.

(ii) Assembly buildings such as Auditoriums, Kalyanamanda-pams, cinema theatres, religious buildings, temples, mosques or churches and other buildings of public assembly or conference.

2.0 metres.

(iii) Institutional building such as--

(a) Government offices ; 2.0 metres.

(b) Hospitals ; 2.4 metres.

(c) Educational buildings such as schools, colleges, research institutions ;

2.0 metres.

(d) Commercial buildings such as private offices, nursing homes, lodges, etc.;

2.0 metres.

(e) All other buildings. 1.5 metres.

(4) Basement Floor.-

(a) The height of basement floor shall not exceed 1.2 metres above ground level and the headroom shall be minimum 2.4 metres.

(b) No part of the basement shall be constructed in the minimum required set back spaces required for the movement of snorkel.

(c) In cases where second basement is proposed for parking and incidental uses, sufficient provision for lighting and ventilation and also for protection from fire to the satisfaction of Directorate of Fire and Rescue Services shall be made.

(d) During the construction of the basement floor, it shall be sole responsibility of the planning permission holder to ensure that the building/structure in the adjoining sites are not weakened/damaged.

(5) The reservation of land for community recreational purposes such as park or play ground required in these regulations shall be as given in Schedule-I.

(6) Conformance to National Building Code of India.--

(a) In so far as the determination of sufficiency of all aspects of structural designs, building services, plumbing, fire protections, construction practice and safety are concerned, the specifications, standards and code of practices recommended in the National Building Code of India shall be fully conformed to and any breach thereof shall be deemed to be a breach of the requirements under these regulations.

(b) Every multi-storeyed development erected shall be provided with,--

(i) lifts as prescribed in National Building Code ;

(ii) a stand-by electric generator of adequate capacity for running lift and water pump, and a room to accommodate the generator;

(iii) an electrical room of not less than 6 metres by

4.0 metres in area with a minimum head room of

2.75 metres to accommodate electric transformer in the ground floor ; and the space for installation of transformers shall conform to the regulation given in Schedule-VIII; and

(iv) at least one metre room of size 2.4 metres by 2.4 metres for every 10 consumers or 3 floors whichever is less. The metre room shall be provided in the ground floor.

(7) Fire safety, detection and extinguishing systems.- -

(a) All building in their design and construction shall be such as to contribute to and ensure individually and collectively and the safety of life from fire, smoke, fumes and also panic arising from these or similar other causes.

(b) In building of such size, arrangement or occupancy that a fire may not itself provide adequate warning to occupants, automatic fire detecting and alarming facilities shall be provided where necessary to warn occupants or the existence of fires, so that they may escape, or to facilitate the orderly conduct of fire exit drills.

(c) Fire protecting and extinguishing system shall conform to accepted standards and shall be installed in accordance with good practice as recommended in the National Building Code of India, (amended from time to time) and to the satisfaction of the Director of Fire and Rescue Services by obtaining a no objection certificate from him.

(8) In cases of residential developments exceeding 50 dwelling units in primary residential use zone, commercial and institutional uses not exceeding 10 per cent of the floor area of the building at lower habitable floor levels, may be allowed (not for any industrial use) as incidental uses required for the occupants of the remaining residential developments within the premises.

(9) The design and plans of the building shall be made and signed by a qualified Civil or Structural Engineer and an Architect who should possess the qualification referred to in the Architects Act, 1972 (Central Act 20 of 1972), so as to become a member of the profession of Architects under the provisions of the said Act. The qualified Engineer or Structural Engineer should also be Class I Licensed Surveyor registered with the Corporation/Local Body concerned.

(10) Display Board.-- The details of the developments for which planning permission issued, date of expiry of permit, etc. shall be displayed in the format prescribed by the Authority on a board of size at least 60 cm. x 120 cm.

(11) In all the development, sewage treatment plant shall be provided and maintained for the disposal of the sewage with design clearance from Pollution Control Board. For smaller development, as per direction of planning authority, septic tank with upflow filters shall be provided and maintained for the disposal of the sewage within the site itself.

(12) In cases where the extent of the site where residential or predominantly residential developments proposed exceeds 10,000 square metre (1 hectare), the developer shall reserve minimum ten per cent of the site area (excluding roads, if any, handed over to local body) and provide housing thereon for lower income groups with dwelling units not exceeding 45 square metre in floor area each, either within the site proposed for Multi-storeyed Building development or in a location within a radius of 5 kilometres from the site under reference. The developer or promoter or owner shall sell these small dwellings only for this purpose. No conversion or amalgamation shall be permissible in these cases of lower income group dwellings.

(13) In residential/predominantly residential developments with dwelling units exceeding 20 in number, the design should include waste management infrastructure with segregation at source and at least a closed non-polluting storage provision for solid waste storage within the premises preferably with direct access from the abutting road shall be provided so that the local body can collect this stored waste from it.

(14) In the interest of the public for better circulation in the area and also to ensure that the proposed development does not block access to the properties around, in cases of large developments where link roads have to be provided for connectivity to the adjoining lands areas, through the site applied for development, the relevant Authority reserves the right to insist the applicant to set apart such road spaces within the site and the applicant shall hand over the same free of cost through a registered gift deed to the Authority or local body designated by it for declaring it as public road. In such cases, set back from these roads to the buildings proposed shall be provided as prescribed in these regulations.

(15) The space set apart for formation of a new road as per Master Plan or Detailed Development Plan or road widening/street alignment shall be transferred to the respective Authority or the Agency or the Local Body through a registered Gift Deed before actual issuance of planning permission. The exact mode of conveyance of the land shall be consistent with the relevant enactment and regulations.

(16) Rain water conservation shall be provided as given in Schedule-V.

1(17) Solar Photo Voltaic system shall be mandatory and shall be provided as prescribed in Schedule IX.]

(18) Civil Aviation height and activity restrictions shall be adhered to. In cases where helipads are proposed at terrace of commercial/industrial multi-storeyed buildings, clearance of civil aviation department shall be produced.

(19) Special regulations for physically disabled shall be adhered to as in Schedule-IV.

(20) Scrutiny of the plan.-- The plan shall be scrutinised as per rule 15 of the Tamil Nadu Multi-storeyed and Public Building Rules,

1973.

3(21) Special Regulation for Hospital buildings shall be adhered to as given in Schedule-XIL] https://www.manupatrafast.com/pers/viewdoctoc.aspx?sPath=Bare%20Acts%20and%20Rules/State/tamil%20nadu/Rules/tamil%20nadu/tamil%20nadu%20town%20and%20country%20planning%20act%201971/DeCoReErVeGuKaSaChTiLoPlAr/DeCoReErVeGuKaSaChTiLoPlAr.htm&col=8Vmp9ozFMb/2ISz1SdixCIRVngsjs/j1lxFukHhUlVjtLjdB0bd4mmFTJWUx/aBSKBdGFQIME6VoesAFaCGBewHrWR8ddcNQuL7JwN7hYU7qHizMrFQj4LFUvb7Bkchar(43)6o706GyNkh4BCUcuVcjmbGhejF08ykNubEvKW4zqo890cktJ88vxBo32cc1YJmu9Dc/5IUlIm3BdNjSABchar(43)2R9TRHZChuWg9X1a6Zdqtl8E2/Y=#F1 https://www.manupatrafast.com/pers/viewdoctoc.aspx?sPath=Bare%20Acts%20and%20Rules/State/tamil%20nadu/Rules/tamil%20nadu/tamil%20nadu%20town%20and%20country%20planning%20act%201971/DeCoReErVeGuKaSaChTiLoPlAr/DeCoReErVeGuKaSaChTiLoPlAr.htm&col=8Vmp9ozFMb/2ISz1SdixCIRVngsjs/j1lxFukHhUlVjtLjdB0bd4mmFTJWUx/aBSKBdGFQIME6VoesAFaCGBewHrWR8ddcNQuL7JwN7hYU7qHizMrFQj4LFUvb7Bkchar(43)6o706GyNkh4BCUcuVcjmbGhejF08ykNubEvKW4zqo890cktJ88vxBo32cc1YJmu9Dc/5IUlIm3BdNjSABchar(43)2R9TRHZChuWg9X1a6Zdqtl8E2/Y=#F3

Where this provision sits

ActDevelopment Control Regulations for Erode/Veuore/Tiruveuore/Coimbatore/Madurai/Gummudipoondi/Kancheepuram/Salem/Chengalpattu/Tiruppur/Tiruchirappalli Local Planning Area
Section5
Marginal noteMulti-storeyed Building
JurisdictionState of Tamil Nadu
StatusIn force as published by the source

Find the provision, not just read it

The full text above is free, and it stays free. What a free CourtMesh account adds is everything you cannot do by reading one page at a time:

  • Search 49,000+ Central and State enactments by what a provision says, not by its number
  • Jump from any section to every judgment that has applied it
  • Search 300 million+ Indian court records alongside the statute
  • Ask a research agent to find and read the case law on a provision for you

Free account. No card. About a minute to create.

Create a free account

Need this as data, not as a page? Development Control Regulations for Erode/Veuore/Tiruveuore/Coimbatore/Madurai/Gummudipoo… is one of 49,000+ enactments on CourtMesh. The Indian court cases API serves the case law that cites these provisions over JSON, with API documentation and plans and pricing. See also the judgment library.