No building, or veranda, or balcony or projection in any building shall be permitted to be erected, re-erected, added to or altered in any case where the distance between such construction and any overhead electric lines, in accordance with the provision of the Indian Electricity Act, 1910(9 of 1910) as amended time to time, and the rules made there under, is less than that specified hereinafter: - (“m” indicates metre) Vertical Clearance Horizontal Clearance

(a) l_ow and Medium voltage lines 25 m. 12 m.

Including servnce lines

(b) High Voltage lines up to and including 11.000 volts 3'7 m' 1'2 m'

(c) High voltage lines above 11.000 volts and up to 3.7 m. 2.0 m.

and including 33 K.volts.

Page 32

(d) For extra high voltage lines 3.7 m. plus 0.3 m for 2.0 m plus 0.3 m for beyond 33.000 volts every additional 33.000 every additional 33 K volts or parts thereof. volts or parts thereof.

43.

Where this provision sits

ActTripura Building Rules — 2017
Section42
Marginal noteDistance from electric lines
JurisdictionState of Tripura
StatusIn force as published by the source

Find the provision, not just read it

The full text above is free, and it stays free. What a free CourtMesh account adds is everything you cannot do by reading one page at a time:

  • Search 49,000+ Central and State enactments by what a provision says, not by its number
  • Jump from any section to every judgment that has applied it
  • Search 300 million+ Indian court records alongside the statute
  • Ask a research agent to find and read the case law on a provision for you

Free account. No card. About a minute to create.

Create a free account

Need this as data, not as a page? Tripura Building Rules — 2017 is one of 49,000+ enactments on CourtMesh. The Indian court cases API serves the case law that cites these provisions over JSON, with API documentation and plans and pricing. See also the judgment library.