Section 70: Conditions to apply where telecommunication lines and power lines are carried on same supports
Central Electricity Authority (Measures relating to Safety and Electric Supply) Regulations, 2023Central Regulations · 2003
(1) Every overhead telecommunication line laid on supports of an electric line shall consist of conductors each 128 THE GAZETTE OF INDIA : EXTRAORDINARY [PART III—SEC.4] having a breaking strength of not less than 270 kgf.
(2) Every telecommunication line laid on supports of an electric line shall be protected against lightning as per relevant standards.
(3) Where a telecommunication line is laid on supports of an electric line of voltage exceeding 650 V, a suitable arrangement shall be made to safeguard any person against injury resulting from contact, leakage or induction between such electric and telecommunication lines.
Need this as data, not as a page? Central Electricity Authority (Measures relating to Safety and Electric Supply) Regulatio… is one of 49,000+ enactments on CourtMesh. The Indian court cases API serves the case law that cites these provisions over JSON, with API documentation and plans and pricing. See also the judgment library.